Yes. A data centre can use appropriately treated recycled water as cooling-tower make-up water, and some facilities already do. That does not mean untreated sewage goes near servers: the water must meet the needs of the equipment, microbial risks must be managed, and local rules govern use and discharge. Recycled make-up water can reduce reliance on drinking water, but an evaporative cooling tower still loses water to evaporation.
What does “recycled water” mean for a data centre?
In this context, recycled water can mean treated municipal wastewater reclaimed for industrial use, water recovered and reused within a facility, or another alternative supply such as HVAC condensate, harvested rainwater or cooling-tower blowdown. These sources are not interchangeable: their quality, availability and treatment needs differ. The U.S. Environmental Protection Agency (EPA) describes treated wastewater as a possible cooling supply in its basic information about water reuse.
It is important to distinguish reclaimed municipal wastewater from the recycling of a data centre’s own cooling water. In the first case, treated effluent from a wastewater facility is delivered to the site. In the second, the operator captures water already used in the cooling system and treats it for another use, often to reduce demand for new make-up water. A project may use one route or combine sources.
Neither route should be confused with a closed-loop coolant circuit serving servers or chips. That is a separate part of the cooling design. A facility can use liquid cooling at the IT equipment and still reject heat through a cooling tower that evaporates water. “Liquid cooled” therefore does not, by itself, mean “water-free.”
Popular on Amazon
- 【90 Degree Full Function USB C Adapter】Supports the latest USB4 standard for up to 40Gbps of bandwidth, 8K video support, and up to 240W Fast charging; Support USB PD 3.1 Extended Power Range (EPR) including 140W, 180W and 240W. Your productivity is easily doubled. *Warm Tip: For the best fit, please make sure the USB-C port is fully exposed; thick or bulky cases may affect compatibility.
- 【Reliable Quality】Made from high-quality, scratch-resistant aluminum alloy, delicate metal frame. get excellent wear resistance and heat dissipation. Non-Slip Design for easier insertion and removal.
- 【Small and portable】Ultra thin size, ultra compact design, a petite physique that matches the minimalist design of your modern laptops. Coming with a slim figure that won't block the port next to the one it's plugged into.
- 【Compatibility】Widely work with most usb c, thunderbolt 4/3 devices. Compatibilit for ROG Ally, Steam Deck, Switch, MacBook Pro, Quest 3 VR headset, Surface Book 2, iPhone 18/17/16/15, Samsung Galaxy S23/S22/S21, Note 20/10, Google Pixel, ChromeBook, etc.
- 【Excellence Customer Support】If you experience any issues or cable failure, simply reach out to our dedicated customer service team. We provide a prompt response within 18 hours, providing you with the necessary technical support to resolve any concerns.
How does recycled water cool a data centre?
The most straightforward arrangement is to treat recycled water to a suitable quality and use it as make-up water in an evaporative cooling system. The tower transfers heat from the facility to the air partly by evaporating water. Minerals and other dissolved material do not evaporate with it, so they become more concentrated in the remaining circulating water.
Operators manage that concentration by removing some water as blowdown and adding make-up water. The U.S. Department of Energy (DOE) describes the approximate balance as make-up water replacing evaporation, blowdown and drift. Drift is water carried out of the tower as small droplets. Recycled water can replace some of the conventional make-up supply, but it does not make evaporation disappear.
Water chemistry sets practical limits on how concentrated the circulating water can become. “Cycles of concentration” describes how much more concentrated the tower water is than its make-up supply. Higher cycles can reduce the amount of blowdown required, but only while scale, corrosion and biological growth remain controlled. The DOE’s cooling-tower management guidance explains why operators need to manage water quality and the tower together rather than treat make-up water as a simple supply substitution.
Free tools Windows power users keep installed
One-click scans. No signup required.
What treatment does recycled water need?
There is no universal treatment recipe. Treatment depends on the source water, the cooling equipment and the quality limits established for that particular system. A project begins by characterizing the proposed supply and setting equipment-specific requirements; the treatment train is then selected to meet them.
Depending on water quality, treatment may include filtration, softening and disinfection, with more advanced processes where needed. A documented project in Quincy, Washington, uses softening, ultrafiltration and reverse osmosis to treat used data-centre cooling water for reuse. That is an example of a site-specific system, not a prescription that every reclaimed-water project needs the same processes.
Also popular on Amazon
- 5-in-1 Connectivity: Equipped with a 4K HDMI port, a 5 Gbps USB-C data port, two 5 Gbps USB-A ports, and a USB C 100W PD-IN port. Note: The USB C 100W PD-IN port supports only charging and does not support data transfer devices such as headphones or speakers.
- Powerful Pass-Through Charging: Supports up to 85W pass-through charging so you can power up your laptop while you use the hub. Note: Pass-through charging requires a charger (not included). Note: To achieve full power for iPad, we recommend using a 45W wall charger.
- Transfer Files in Seconds: Move files to and from your laptop at speeds of up to 5 Gbps via the USB-C and USB-A data ports. Note: The USB C 5Gbps Data port does not support video output.
- HD Display: Connect to the HDMI port to stream or mirror content to an external monitor in resolutions of up to 4K@30Hz. Note: The USB-C ports do not support video output.
- What You Get: Anker 332 USB-C Hub (5-in-1), welcome guide, our worry-free 18-month warranty, and friendly customer service.
Reverse osmosis (RO) separates water from many dissolved constituents, but it does not make residuals vanish. The Quincy project manages concentrated salts separately. In general, operators need a plan for treatment residuals such as brine, as well as for tower blowdown. DOE notes that RO can recover blowdown for use as make-up water, while adding energy and maintenance demands.
As a result, the right question is not simply whether water has been “recycled.” It is whether the source and treatment produce water appropriate for the planned equipment, and whether the resulting residual streams can be managed lawfully and reliably.
Crashes, No Sound, or Screen Glitches?
Random freezes, missing sound and display glitches usually trace back to one bad driver. Find and replace yours safely.Free scan · under a minuteWindows Errors? Fix Them Before They Spread
Repair common Windows errors and clear accumulated junk for a smoother, more stable PC - no reinstall needed.Free scan · no reinstallIs recycled-water cooling safe?
It can be operated with health protections, but source-water treatment alone is not a substitute for managing the cooling tower. Cooling towers can aerosolize water, and the U.S. Centers for Disease Control and Prevention (CDC) warns that aerosols carrying Legionella can pose a public-health risk. That makes prevention and ongoing operation central parts of the design.
Facilities should use a site-specific water-management programme, maintain appropriate disinfection and monitoring, and avoid conditions such as stagnant water that can support microbial growth. The CDC’s cooling-towers module provides guidance on managing this risk. A reclaimed source must be managed as part of the system; the word “treated” is not, on its own, proof that the tower is safe.
Nor does a handheld conductivity reading demonstrate microbiological safety. Conductivity can help an operator assess mineral concentration and manage cycles of concentration, but it does not establish that water is free of pathogens. Monitoring tools answer particular operating questions; they do not replace microbiological controls, an appropriate water-management plan or engineering judgement.
Also popular on Amazon
- Sleek 7-in-1 USB-C Hub: Features an HDMI port, two USB-A 3.0 ports, and a USB-C data port, each providing 5Gbps transfer speeds. It also includes a USB-C PD input port for charging up to 100W and dual SD and TF card slots, all in a compact design.
- Flawless 4K@60Hz Video with HDMI: Delivers exceptional clarity and smoothness with its 4K@60Hz HDMI port, making it ideal for high-definition presentations and entertainment. (Note: Only the HDMI port supports video projection; the USB-C port is for data transfer only.)
- Double Up on Efficiency: The two USB-A 3.0 ports and a USB-C port support a fast 5Gbps data rate, significantly boosting your transfer speeds and improving productivity.
- Fast and Reliable 85W Charging: Offers high-capacity, speedy charging for laptops up to 85W, so you spend less time tethered to an outlet and more time being productive.
- What You Get: Anker USB-C Hub (7-in-1), welcome guide, 18-month warranty, and our friendly customer service.
What approvals and planning does a project need?
Requirements depend on the source, intended use and location. In the United States, EPA says states generally have primary authority over water reuse, and requirements vary with the source and use. A project must confirm the applicable state and local reuse conditions rather than assume a single nationwide quality threshold or permit applies everywhere.
Planning should cover the complete path from supply to discharge:
- Source and geography: Confirm the seasonal volume available, how close it is to the site, and whether the source can meet demand when the facility needs it. Pipes, pumping and storage can make a distant supply costly or impractical.
- Quality and equipment: Test the prospective water and set limits for the actual cooling equipment. Treatment needs depend on both the source and those limits.
- Residuals and discharge: Establish how blowdown, brine and other treatment residuals will be handled, and confirm any applicable discharge conditions.
- Operations and safety: Include tower disinfection, monitoring and water-management responsibilities in the operating plan.
- Whole-system trade-offs: Account for capital and operating costs, treatment and pumping energy, source reliability, potable-water displacement, withdrawals, evaporation, health controls and residual disposal.
These questions connect water reuse to infrastructure beyond the data-centre fence. PNNL frames a cooling-tower reuse project as a system involving a source, storage, treatment, distribution and cooling equipment. The availability of treated effluent nearby does not guarantee a viable connection: EPA’s Quincy case notes that distance can make connections expensive for other local facilities.
Where is recycled water already used for data-centre cooling?
Publicly documented examples show that different reuse arrangements are possible. Their reported figures describe particular projects or operators, not a universal saving that can be applied to another site.
Quincy, Washington: reuse of used cooling water
EPA’s 2023 case study describes a Microsoft–city utility project that began operating in 2021. It treats used data-centre cooling water with softening, ultrafiltration and reverse osmosis, and manages concentrated salts separately. EPA estimated that the project would offset 138 million gallons of demand per year and reported an overall project cost of $31 million. These are figures for that project, not a per-facility benchmark. The source is industrial cooling water that has already been used, not municipal sewage supplied directly to the data centre. EPA’s case study is titled Water Reuse Case Study: Quincy, Washington.
Quick wins for a faster PC:
Clear out junk files and repair common Windows errorsFree Scan →Fix the driver behind crashes, sound loss and screen glitchesFind Drivers →Repair Windows errors before they cause bigger problemsFix Now →Also popular on Amazon
- Portable and powerful USB-C HUB: BENFEI USB Type-C HUB, with super-soft and knot-free silicone woven design cable, meets most mobile office needs. Compact, lightweight, stylish, and powerful portable USB C Hub equipped with 1 x HDMI port, 1 x 100W charging, and 3 x USB ports. 18-month warranty, 24-hour response, to ensure you feel at ease when using our product.
- Design centered on comfort and reliability: Thanks to BENFEI's end-to-end in-house cable production capability, in-house PCBA and assembly capability, using the industry's most advanced silicone woven design and process, 20cm cable in length, no knots, super-soft, the HUB is easy to use in all scenarios: laptop, tablet, stand etc. Super-soft, 25000+ life cycles, to meet your daily carrying and office needs.
- 100W Charging: Support up to 90W USB C pass-through charging via Type-C port to keep your laptop powered. 10W is reserved for other interface operations. No data and video function on the Type-C port.
- 4K HDMI Display: The HDMI port supports media display at resolutions up to 4K 30Hz, keeping every incredible moment detailed and ultra vivid. Please note that the C port of the Host device needs to support video output.
- Transfer Files in Seconds: Transfer files and from your laptop at speeds up to 10 Gbps with USB A 3.2 port. Extra 2 USB A 2.0 ports are perfectly for your keyboards and mouse.
Loudoun County, Virginia: reclaimed municipal water
Non-potable reclaimed water from the Broad Run Water Reclamation Facility supplies cooling to some data centres in Loudoun County. EPA’s 2026 Water Reuse Action Plan 2.0 reports that more than 745 million gallons were supplied for cooling in 2025. That is a reported supply volume, not a measured water saving for any one facility. The plan is available as an EPA PDF.
Douglas County, Georgia: municipal wastewater reuse
EPA reports that Google cools its data centres in Douglas County with recycled municipal wastewater. The company treats unevaporated leftover water before returning it to the Chattahoochee River. The cited EPA passage does not provide a site-specific savings figure, so none can be inferred from the example.
Why operator-wide figures need careful reading
In 2026, Microsoft reported an average water-usage effectiveness (WUE) of 0.27 litres per kilowatt-hour for its owned fleet in 2025. WUE relates water use to IT electricity; it does not say what share of that water was recycled. Microsoft also reported that recycled, reused or non-potable sources accounted for 74% in Quincy, 99% in Singapore and 79% in San Antonio. Those combined categories are not percentages of reclaimed municipal wastewater alone. The company’s figures and definitions appear in its 2026 account of its water-intensity work.
Independent reader supportYour contribution helps us test, update, and keep practical guides available for everyone.Does recycled water reduce drinking-water use?
Using treated effluent or another non-potable source can displace some potable make-up water, which is one reason a project may be considered. But a volume supplied is not automatically the same as a volume saved: the result depends on what source the facility would otherwise have used, how much water the cooling system consumes, and how the project’s boundaries are counted.
It is also necessary to distinguish reduced potable-water demand from reduced total water consumption. An evaporative tower still loses water through evaporation, and the facility may need to replace blowdown and drift. A complete comparison should account for source withdrawals, evaporation, treatment and pumping energy, water reliability and residual disposal—not just the label on the make-up supply.
Also popular on Amazon
- 【Read before You Buy】 Note: This adapter is USB 2.0 version and cannot transmit HDM, VGA, or other video signals. Nevertheless, they are fully capable of charging devices,duplicating files, and can be seamlessly integrated with USB-C earphones, wireless network adapters, and SD card adapters.
- 【Easy to Use and Safe】Thanks to modern manufacturing techniques, we've made these adapters sufficiently compact so that they can remain inserted in your device without noticeable protrusion or inconvenience. This means you don't have to constantly plug and unplug them, reducing the likelihood of wear and misalignment, and making them more convenient to carry around.
- 【Reliable Quality】Engineered for enhanced durability, durable aluminum alloy shell material,get excellent wear resistance and heat dissipation,the male USB C and female USB connectors & the male USB and female USB C connectors are designed to be plugged and unplugged up to 20000 times. Provides data transfer, device charging, memory space expansion, and additional computer peripherals.
- 【Think more for you】Do you need to connect a USB-C-enabled device to an odd device that only has USB-A ports? Then these USB-A male to USB-C female adapters are made for you.Simply insert the adapter into the USB-A port on the device, and you can instantly connect your USB-C device to the device that originally didn't have the correct connection port.
- 【Trusted xiwxi Quality and Service】As a responsible brand seller, you will receive xiwxi's 12-month Quality assurance and lifetime friendly customer service, you're not just buying a product,you're investing in peace of mind with all-round quality and exceptional customer service.
What are the alternatives to reclaimed municipal water?
Reclaimed municipal effluent is one option, not the only one. A facility may recover and treat its own cooling water, use other alternative supplies such as condensate or rainwater where suitable, or change how heat is rejected. The practical choice depends on local water availability, treatment needs, equipment, energy, health controls, permits, distance to infrastructure and cost.
Hybrid or dry heat-rejection systems can reduce or avoid evaporative cooling water in suitable designs, but they involve a different heat-rejection arrangement and must be assessed on their own operational merits. The DOE’s discussion of direct liquid cooling includes configurations that still reject heat through a cooling tower. Microsoft has separately described a zero-water-evaporation design using a different heat-rejection approach. Those examples reinforce that the cooling method at the server and the method used to reject heat from the facility are related but distinct design decisions.
How should an operator assess a proposed reuse project?
A useful assessment compares the full water system rather than asking only whether a recycled source is available. The sequence below turns the main design and operational questions into decision points.
Do these 3 things before closing this tab:
1Clear out junk files and repair common Windows errors2Scan for outdated or missing drivers - takes under a minute3Repair Windows errors before they cause bigger problems- Define the outcome. Identify whether the priority is to reduce potable-water demand, limit withdrawals from a stressed source, improve supply reliability or reduce total water use. Those goals are related but not identical.
- Compare available sources. Determine seasonal quantity, reliability and distance for reclaimed municipal water, onsite recovery and other suitable supplies. Include storage and distribution needs.
- Set equipment-specific water limits. Characterize the source and establish what the cooling system requires before selecting treatment. Do not assume one facility’s treatment train will suit another source.
- Design for water chemistry and system control. Set operating limits for concentration, scaling and corrosion, and determine how blowdown will be managed. Increasing cycles of concentration is only useful while the tower remains controlled.
- Plan health controls and residual handling. Integrate disinfection, monitoring and a water-management programme; identify the permitted routes for blowdown, brine and other residuals.
- Evaluate the whole-life trade-off. Compare capital and operating costs, treatment and pumping energy, reliability, evaporation, potable-water displacement and disposal obligations. A water source can be beneficial on one measure and burdensome on another.
For operators monitoring tower concentration, DOE discusses conductivity as a way to compare mineral concentration in make-up and circulating water and describes automated blowdown control. A conductivity instrument or controller can support that specific operating task, but neither can establish pathogen safety or replace a qualified system design.
Frequently Asked Questions
Can reclaimed wastewater be used in a data centre’s direct-to-chip cooling loop?
It should not be assumed that water acceptable as cooling-tower make-up is also suitable for a server-side liquid-cooling circuit. The two systems have different equipment and water-quality requirements, so a design must specify and validate the quality needed for each loop.
Does recycled water have to be drinking-water quality before it reaches a cooling tower?
Not necessarily; reuse requirements are tied to the intended use and location, rather than a single universal drinking-water standard. The operator still needs to establish water-quality limits for the cooling equipment and meet applicable local reuse conditions.
Can a data centre reuse cooling-tower blowdown?
It can be treated for reuse in some systems; DOE notes that reverse osmosis can recover blowdown for use as make-up water. The approach also creates treatment residuals and adds energy and maintenance demands, so the recovery process needs its own operational and disposal plan.
What’s actually slowing this PC down?
Pick the symptom - the matching free tool is one click away.
Does recycled cooling water create Legionella risk by itself?
The relevant concern is the cooling tower’s water management and potential aerosol exposure, not simply whether the source was recycled. CDC guidance focuses on controls such as an appropriate water-management programme, disinfection and monitoring.