There is no single water or electricity figure for a “typical” data center: a facility’s footprint depends on its IT load, utilization, cooling design, climate and power supply. For the United States, Lawrence Berkeley National Laboratory (LBNL) estimated that data centers used 192 terawatt-hours (TWh) of electricity in 2024, equal to 4.7% of U.S. electricity consumption. That estimate excludes cryptocurrency mining. Water is harder to summarize: facilities may consume it directly for cooling, and power generation can consume water upstream, but a comparable current U.S. total covering both pathways is not established by the cited primary sources.

How much electricity do U.S. data centers use?

LBNL’s June 2026 update estimates U.S. data-center electricity use at 192 TWh in 2024, or 4.7% of U.S. electricity consumption. The estimate comes from a bottom-up model using equipment shipments, device power use, facility types and locations. Its scope excludes cryptocurrency mining, so the figure should not be described as including every computing operation sometimes called a data center.

A terawatt-hour is one billion kilowatt-hours. The national total is useful for understanding the scale of data-center demand, but it is not a measure of the electricity used by one building, one server, or one company. Individual facilities differ greatly in size and in how intensively their equipment runs. A national percentage also says nothing by itself about whether a particular facility’s power is available at a particular hour or how much electricity it uses per computing task.

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.

What the U.S. forecast means

LBNL’s 2030 Reference Case estimates data-center consumption at 649 TWh, or 11.8% of forecast U.S. electricity use. This is a modeled scenario, not a guaranteed outcome. LBNL gives a combined uncertainty range of 521–843 TWh, equal to 9.5–15.3% of projected U.S. electricity use. The range reflects sensitivity to assumptions such as server deployment and operating conditions; it is more informative than treating the reference case as a precise prediction.

#1 Best Overall
Compressed Air Duster,130000RPM Super Power Cordless Air Duster,Rechargeable Brushless Blower,3 Gear Adjustable Blower with LED Light,Dust Remover for Computer/House/Outdoor/Car
  • Powerful Turbo Fan:CAGIWIRU Electric Air Duster have reached speed up to 130000RPM,Can efficient remove dust and debris.With LED light and Three Adjustable Speed to meet with different cleaning tasks.
  • With Attached USB C Fasting Charging cable.Charing 3 hours,Enjoy up to 240 minutes of use on the lowest setting, For third speed can use for 25mins.with four charging options to meet with your needs.
  • Wide Application:Upgraded attached 5 different nozzles,making it suitable for a variety of scenes, such as car,pet, pc, keyboards, and other electronic devices. It also serves for office and home clean duster.
  • Handy Design & Portable:Cordless air duster electric nozzle is Light weight and small size, design and comfortable to hold and space saving, convenient to carry around. You can put it in your room or inside the car without taking up space.
  • Warranty & Support: Our Electric air duster comes with 5 years warranty and 24/7 customer service. During this period, if you have any questions,pls kindly feel free to contact us.

Keep those forecast figures separate from historical estimates. DOE’s December 2024 announcement, based on LBNL’s 2024 report, said data centers used 176 TWh in 2023 and forecast 325–580 TWh in 2028. LBNL’s June 2026 update supersedes that earlier estimate for current U.S. electricity framing. The different numbers reflect different report vintages and modeling, not a direct measurement showing that consumption suddenly changed from one figure to another.

How much electricity do data centers use worldwide?

The International Energy Agency (IEA) estimated global data-center electricity consumption at 460 TWh in 2024. In its Base Case, the IEA projects more than 1,000 TWh in 2030 and 1,300 TWh in 2035. These global estimates and LBNL’s U.S. estimate come from separate analyses with their own methods and boundaries. They should be attributed to their respective source and year rather than combined as if they were a single standardized dataset.

Forecasts depend on how much computing equipment is installed and used, as well as how efficiently the equipment and supporting systems operate. A data center’s IT load—the electricity used by computing and storage equipment—is only part of the facility’s electricity demand. Power is also used by the systems that distribute electricity and remove heat. The share used for cooling and other support equipment varies with facility design and operating conditions, so an IT capacity figure alone does not give the building’s total electricity use.

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.

Where does data-center electricity come from?

Electricity can reach a data center from the local grid, from onsite generation, or from a combination of sources. The physical generation mix serving the facility depends on its location and on the power system’s operation. The IEA’s 2025 assessment estimates the current global mix for data centers at approximately 30% coal, 27% renewables, 26% natural gas and 15% nuclear. The shares are approximate and do not add to 100%, in part because of rounding and other sources.

Rank #2
EVEO® Screen Cleaner Spray Kit (Streak-Free) TV Screen Cleaner for Smart TV, Lcd, LEd, Oled | Computer Screen Cleaner Spray and Wipe Microfiber Cloth - TV, Monitor, Laptop, iPad, Car - 6.7oz 1 Pack
  • Screen Cleaner is Your Screen’s New Bestfriend! - EVEO is proud to present a screen cleaner that’s perfectly suited for your TV. Meet your new screen cleaner, computer screen cleaner, laptop cleaner, iPad cleaner, Macbook,tv cleaner or any other electronic device. Our screen cleaner spray and wipe along with the included plush microfiber cloth, easily removes dust, fingerprints & other smudges on the screen’s surface. Clean effectively for a streak-free screen
  • Gentle on your Screens - Our screen cleaner spray and wipes is compatible to be used even for the most sensitive LCD, LED, CRT, and OLED screens in proper use. Be at ease knowing that this product is compatible with all the major brands: LG, SONY, Samsung, Sharp, iPad, iPhone, Android screens, Kindle, PC monitors - we’ve got you covered! Can be used as LCD screen cleaner, tv cleaner, smart tv screen cleaner, and more
  • Premium Super Soft Plush Microfiber Cloth - Included in this efficient screen cleaning kit. This screen cleaner spray and wipe has our signature plush microfiber cloth specially designed to comply with screens and monitors and leave them streak-free. Has been shown to effectively absorbs stubborn stains, zero streaks, and no fiber shedding. Always use this together with our screen cleaner for the best results
  • Easy-to-Use Screen Cleaner Kit + microfiber cleaning cloth - The EVEO Screen Cleaning Kit will easily be your new favorite tool when it comes to taking care of the things you love most, quick and easy solution for a streak-free screen. Simply screw on the sprayer gun on the screen cleaner bottle. Spray the cleaning liquid onto the microfiber cloth, then wipe the screen until desired cleanliness & shine is achieved.
  • Quality Screen Care Kit Worth Purchasing - Enjoy a convenient Screen Cleaner anytime, anywhere you need it. Your satisfaction is our top priority. We stand behind the quality of our products and that’s why, you shouldn’t be worrying at all. We manufacture the Best Screen Cleaner. and can be used for laptop cleaning kit, laptop screen cleaner, tv screen cleaner for smart tv. MacBook screen cleaner, monitor cleaner or screen cleaner spray for electronic devices with microfiber cleaning cloth

The U.S. mix in the IEA analysis differs from that global average. Natural gas supplies over 40% of data-center electricity, renewables 24%, nuclear around 20% and coal around 15%. The IEA’s U.S. Base Case projects that between 2024 and 2030, natural-gas generation for data centers will increase by more than 130 TWh annually, while renewable generation will increase by 110 TWh. Those additions are scenario projections, not guaranteed generation outcomes.

Geography and period IEA estimate or projection How to read it
Global, current mix assessment (IEA, 2025) Coal about 30%; renewables about 27%; natural gas 26%; nuclear 15% Approximate physical generation mix; regional mixes differ.
United States, current mix assessment (IEA, 2025) Natural gas over 40%; renewables 24%; nuclear around 20%; coal around 15% U.S.-specific mix, not the global average.
United States, 2024–2030 Base Case (IEA, 2025) Annual natural-gas generation for data centers rises by over 130 TWh; renewables by 110 TWh Projected additions in a scenario, not a measured result.

Physical electricity and renewable-energy contracts are different measures

The IEA describes the physical fuel mix supplying data centers through local grids and onsite generation. That is not necessarily the same as an operator’s contractual or annual renewable-energy procurement claim. A company may buy renewable-energy certificates or sign a power purchase agreement while its facility draws from a grid whose generation mix changes hour by hour. The contract can describe an accounting or procurement arrangement; it does not, on its own, establish that renewable electricity physically served the building at every moment.

When comparing claims about a facility’s electricity, ask what is being counted: the physical electricity supplied at a location, or electricity matched through contracts over a reporting period. Also check whether the number describes annual energy, peak capacity, or a share of total demand. These are different measurements and should not be substituted for one another.

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.

How much water does a data center use?

Water use has at least two distinct pathways. A facility can consume water onsite to remove heat, while electricity generation can consume water upstream. The two quantities have different boundaries and should not be blended without a clearly stated accounting method. A comparable current national total for U.S. data centers that cleanly combines direct facility water consumption and water consumed in electricity generation is not established in the cited primary sources.

Rank #3
BladeHawks RGB Gaming Mouse Pad Extra Large Extended 31.5x12 Inch-Black
  • 【Large size】:Measuring 800 x 300 mm/ 31. 5×12 inches, which is wider and taller than others. Large mouse pad can perfectly fit your keyboard and mouse of any size, and there is also ample space for peripherals such as phones, tablets, etc.
  • 【LED backlight mouse pad】:Blade Hawks RGB mouse pad provides 7 static modes and 7 dynamic modes will give you the options you are looking for. Power-off memory function remembers the last lighting mode you selected. The super glow fiber Chroma will give you a colorful gaming setup that you want.
  • 【Anti-slip rubber base】:Made from Natural rubber, this gaming mousepad will firmly grip your desktop, allowing you to enjoy the ultimate precision in the games you are most passionate about. It also comes with a texture that enhances this ability even further.
  • 【Smooth and waterproof surface】: Micro-textured cloth surface, for extremely precise mouse control and a smooth movement. When liquid splashes on the gaming mouse pad, it forms water droplets and slides down. Will not delay your work or gameplay.
  • 【Plug and play】: This mouse and keyboard pad is powered by USB, plug and play, no driver required. One button control light modes. Press one time to change the lighting mode, press twice to change the brightness, press and hold about 3 seconds turn ON/OFF.

Direct water use at the facility

Some cooling systems reject heat through cooling towers. In the arrangement described by the U.S. Department of Energy’s Federal Energy Management Program (FEMP), heat moves from IT equipment through cooling loops to a tower, where evaporation releases heat to the atmosphere. Evaporation is a direct water-consumption pathway. Towers also discharge some water as blowdown to control the concentration of dissolved minerals. The amount of water required depends on the IT heat load and the efficiency of each stage of the cooling system.

Not every data center uses the same cooling design or consumes the same amount of water. A facility’s water footprint depends on its equipment load, cooling technology, operating settings and local conditions. A site-level number therefore needs its boundary and time period: for example, whether it counts only water consumed inside the facility or also water associated with electricity supply. Without those details, two reported figures may not be comparable.

Indirect water use from electricity generation

Power plants may consume water while generating the electricity that a data center uses. The amount depends on the generation technologies in the relevant power supply. This is an upstream impact, not water delivered to the data center’s cooling system. A facility with low direct water use can still be associated with water consumption in electricity generation; conversely, a direct cooling-water figure does not capture that upstream use.

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.

Water accounting also distinguishes withdrawal from consumption. Withdrawal is water taken from a source. Consumption refers to water not returned to the same watershed in the same condition or time frame. Because the terms describe different things, they cannot simply be added or compared as if they were interchangeable. Any combined footprint should say which measures it includes and how it treats water returned after use.

Rank #4
Sale
Vaydeer Wrist Rest for Keyboard and Mouse, Computer Ergonomic Wrist Support Pad, Soft Memory Foam Arm Cushion for Desk, Palm Hand Office Laptop Typing
  • 【Softer and More Comfortable】Vaydeer wrist rest has unique diamond pattern, which is the combination of softness and aesthetics. The materials of wrist rest are improved into higher quality memory foam and covered with silky smooth lycra. The computer wrist rest makes you as comfortable and cushiony as like rest your wrists on clouds.
  • 【Ergonomic Wrist Saver】The wrist rests for keyboard and mouse comes with a 17.32×3.15×0.83 inch keyboard wrist pad and a 5.94×3.15×0.83 inch mouse wrist support. Based on ergonomic design, the unique concave shape is the perfect fit for your wrist joints. The wrist rest pad fits most computer keyboards and laptops, improve hand and wrist posture, release your wrist and arm stress.
  • 【Non-Slip Rubber Bottom】Featuring an anti-skid silicone base on the bottom, this wrist keyboard support stays firmly in place on your desk, preventing the padding from sliding around, ensuring stable and consistent wrist support during extended computer sessions.
  • 【Better Experience & Pain Relief】Our keyboard arm rest is beneficial to alleviate the soreness caused by direct contact and friction between your arm and a hard desk surface, reducing the risk of wrist fatigue or carpal tunnel. The soft texture of memory foam can evenly distribute the pressure around your wrists and provide good support with just enough give.
  • 【Helpful in Multiple Scenarios】Whether you're working, studying, writing, typing, gaming, this keyboard and mouse rest combo is an essential accessory to add comfort and support to your hands and wrists. It’s also a great gift for men, women, family, friend, coworker, gamer, teacher, etc.

What WUE measures—and what it leaves out

Water-usage effectiveness (WUE) is a site-based metric relating facility water use to IT energy use, commonly expressed in liters per kilowatt-hour. It can help describe direct facility water intensity relative to computing energy. To interpret a WUE figure, check its reporting boundary and period, and whether the reported water quantity is withdrawal or consumption.

WUE does not, by itself, count water consumed to generate the facility’s electricity. It is therefore not a complete measure of a data center’s total water impact. Two sites’ WUE values are most useful when the underlying accounting boundaries and operating conditions are clear; the metric alone does not explain their total water use or the water impacts of their power supplies.

Independent reader supportYour contribution helps us test, update, and keep practical guides available for everyone.Support on Ko-Fi

How cooling choices affect water and electricity

Cooling systems involve trade-offs. FEMP describes air-side economizing—using cool outside air when conditions allow—as a way to reduce cooling-system energy and water use. The potential savings depend on climate and operating set points, so it is not a guaranteed result for every site. Whether outside air is useful depends on local conditions and how the facility is operated.

What’s actually slowing this PC down?

Pick the symptom - the matching free tool is one click away.

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.

For cooling towers, FEMP notes that increasing cycles of concentration from three to six can reduce makeup-water requirements by 20% and blowdown by 50%, citing its Cooling Tower Best Management Practice. These are system-level guidance examples, not universal data-center savings. Actual results depend on the tower and its operating conditions. Makeup water is the water added to replace losses and maintain operation; reducing blowdown does not mean evaporation or all water consumption disappears.

Best Value
Sale
Under Desk Cable Management Tray No Drill, Metal Mesh Cable Management Under Desk with Clamp Mount, 2 Hole Cable Tray with Wire Management and Cord Organizer for Home Office Standing Desk
  • 【No Drill Mounted】Cable management tray can be assembled in as little as 3 minutes or less-simply. Side clips easily clampe the edge of desk, pass through the holes on the sides, and secure excess cables with baskets. Desk cable management supports inward or outward installation to meet your needs in different scenarios, and provides you with great convenience when collecting and organizing wires.
  • 【Rubber Pad Protects Desk】Wire organizer under desk built-in soft rubber pads on the clamp protect your desk from scratches, so you will not damage your furniture or office.
  • 【Sturdy and Beautiful】Cord management under desk is made of high-quality carbon steel and holds about 15 lbs. The wire basket has 2 holes on each side of the tray to enable your cables to pass freely. Cable baskets are suitable for desk thickness use from 0.4" to 2.4".
  • 【Space Saving & Keep Organized】Desk cable management tray holds all your power cords, outlet strips, USB hubs and computer transformers hidden from your feet, and the data cables will not enter the vacuum cleaner to keep your desk clean and tidy. Desk wire organizer is also suitable for use in the kitchen and outdoors.
  • 【Reduce Safety Risks】Cable tray under desk keeps all plugs away from your kids, no more worry about tripping. Using 2 holes wire tray saves extra space, helps you easily cabling and wire protection. The mesh design is not easy to accumulate dust, but avoids safety accidents caused by messy wires.

How to judge a data-center water or power claim

Before comparing a facility’s footprint with a national estimate or another site, identify the accounting boundary. A clear claim should make it possible to answer the following questions:

  • Where? Is the figure for one facility, a region, the United States or the world?
  • When? Does it describe a measured historical year or a modeled forecast?
  • What boundary? Does it include only direct facility use, or upstream electricity-generation impacts too?
  • Which water measure? Is it withdrawal, consumption, or both, reported separately?
  • Which electricity measure? Is it TWh of energy, peak power capacity, or a percentage of national consumption?
  • Which supply accounting? Does the generation mix describe physical grid and onsite supply, or contractual procurement over a period?
  • How certain is it? Is a number a central scenario, a range, a facility measurement, or a forecast?

These checks matter because a facility’s direct cooling-water number, a company’s renewable procurement total and a national electricity forecast answer different questions. A useful comparison keeps the unit, geography, year and boundary visible rather than reducing the result to one headline figure.

What can and cannot be concluded from national figures

The strongest current national electricity anchor in the cited U.S. analysis is LBNL’s 192 TWh estimate for 2024, with its cryptocurrency-mining exclusion stated. The 2030 numbers describe a reference scenario and a wide uncertainty range. The IEA’s global and U.S. mix estimates show that data-center electricity is supplied by different combinations of fuels and technologies depending on region, and that contractual renewable procurement should not be mistaken for the physical grid mix.

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.

For water, the defensible answer is more qualified: direct cooling consumption and upstream power-generation consumption are real but distinct pathways, while the cited primary sources do not establish a comparable current U.S. total combining them. A single water figure without a defined boundary, measurement type and year can obscure more than it explains.