Data centres use water mainly to move heat away from servers and reject that heat to the environment. In a cooling-tower system, water circulates through heat exchangers, some of it evaporates at the tower, and some is drained as “blowdown” so minerals do not build up. Other designs use outside air, air-cooled equipment or closed liquid loops that can avoid ongoing cooling-water evaporation. The amount withdrawn, consumed, recirculated and discharged depends on the facility’s design, climate, water quality and operating practices.
Why a data centre needs cooling
Servers, storage systems, networking equipment, power supplies and other electrical components turn much of the electricity they consume into heat. That heat is produced continuously, including overnight and during periods when demand is lower. If it is not removed, component temperatures can exceed operating limits, causing throttling, failures or automatic shutdowns.
Cooling is therefore a heat-removal chain rather than a single appliance. Fans, pumps, heat exchangers, chillers, cooling towers and control systems work together to transfer heat from the electronics to a final heat sink, usually outdoor air. Water may be part of that chain, but it is not always consumed in the same way.
The Tool Desk
Outbyte Driver Updater FREEScan for outdated or missing drivers - takes under a minuteDriver Scan →Outbyte PC Repair FREEClear out junk files and repair common Windows errorsFree Scan →How water moves through a typical cooling-tower system
The U.S. Department of Energy’s Federal Energy Management Program (DOE FEMP) describes a common arrangement in four linked stages. The exact equipment varies by site, but the direction of heat flow is broadly the same.
#1 Best Overall
- Powerful Turbo Fan:CAGIWIRU Electric Air Duster have reached speed up to 130000RPM,Can efficient remove dust and debris.With LED light and Three Adjustable Speed to meet with different cleaning tasks.
- With Attached USB C Fasting Charging cable.Charing 3 hours,Enjoy up to 240 minutes of use on the lowest setting, For third speed can use for 25mins.with four charging options to meet with your needs.
- Wide Application: attached 5 different nozzles,making it suitable for a variety of scenes, such as car,pet, pc, keyboards, and other electronic devices. It also serves for office and home clean duster.
- Handy Design & Portable:Cordless air duster electric nozzle is Light weight and small size, design and comfortable to hold and space saving, convenient to carry around. You can put it in your room or inside the car without taking up space.
- Economical &Reusable: Built durable materials with a long-lasting battery,our CAGIWIRU air duster it's a sustainable alternative to disposable air cans.
- IT equipment generates heat. Chips and other electrical components warm the air or liquid around them.
- Room or rack cooling captures that heat. Air handlers or liquid-cooling hardware transfer heat into a chilled-water loop or another intermediate circuit.
- A chiller moves heat into a condenser-water loop. The chiller’s refrigeration cycle separates the indoor cooling loop from the loop that will reject heat outdoors.
- A cooling tower rejects heat to the atmosphere. Warm condenser water is distributed over tower fill while fans or natural airflow move air through it. A small portion of the water evaporates; that phase change carries heat away.
The cooled condenser water returns to the chiller and repeats the cycle. Water that evaporates must be replaced with makeup water. The tower also loses water through drift, when tiny droplets leave with the exhaust air, and through leaks or maintenance activities.
“Water used” can mean four different things
Reports can appear contradictory because they use different boundaries and definitions. A facility may withdraw water from a municipal supply, consume some through evaporation, discharge some as wastewater and recirculate the rest many times. These quantities should not be treated as interchangeable.
- Withdrawal: water taken from a source such as a utility, river, aquifer or reclaimed-water network.
- Consumption: water that does not immediately return to the source being measured. In an evaporative tower, the principal consumed portion becomes atmospheric water vapour.
- Discharge: water sent to a sewer, treatment plant or permitted receiving system. Cooling-tower blowdown is a common discharge stream.
- Recirculation: water kept in a loop and used repeatedly. Recirculated water can support many heat-transfer cycles while only makeup water enters the loop.
A facility can therefore have high internal circulation but relatively modest withdrawals, or low direct consumption but substantial indirect water use associated with the electricity that powers it. Any number needs its boundary and measurement period.
Recommended Free Tools
What evaporation does in a cooling tower
Evaporation is the tower’s primary heat-rejection mechanism. As liquid water changes to vapour, it removes a large amount of heat without requiring all of the circulating water to leave the system. The vapour joins the atmosphere; it is not normally captured and piped back to the data centre.
Evaporation also concentrates dissolved minerals. Water entering a tower contains salts and other dissolved material, and those substances remain when water vapour leaves. If concentration rises too far, scale can form on heat-transfer surfaces, corrosion can accelerate and biological-control requirements can change.
Rank #2
- Screen Cleaner is Your Screen’s New Bestfriend! - EVEO is proud to present a screen cleaner that’s perfectly suited for your TV. Meet your new screen cleaner, computer screen cleaner, laptop cleaner, iPad cleaner, Macbook,tv cleaner or any other electronic device. Our screen cleaner spray and wipe along with the included plush microfiber cloth, easily removes dust, fingerprints & other smudges on the screen’s surface. Clean effectively for a streak-free screen
- Gentle on your Screens - Our screen cleaner spray and wipes is compatible to be used even for the most sensitive LCD, LED, CRT, and OLED screens in proper use. Be at ease knowing that this product is compatible with all the major brands: LG, SONY, Samsung, Sharp, iPad, iPhone, Android screens, Kindle, PC monitors - we’ve got you covered! Can be used as LCD screen cleaner, tv cleaner, smart tv screen cleaner, and more
- Premium Super Soft Plush Microfiber Cloth - Included in this efficient screen cleaning kit. This screen cleaner spray and wipe has our signature plush microfiber cloth specially designed to comply with screens and monitors and leave them streak-free. Has been shown to effectively absorbs stubborn stains, zero streaks, and no fiber shedding. Always use this together with our screen cleaner for the best results
- Easy-to-Use Screen Cleaner Kit + microfiber cleaning cloth - The EVEO Screen Cleaning Kit will easily be your new favorite tool when it comes to taking care of the things you love most, quick and easy solution for a streak-free screen. Simply screw on the sprayer gun on the screen cleaner bottle. Spray the cleaning liquid onto the microfiber cloth, then wipe the screen until desired cleanliness & shine is achieved.
- Quality Screen Care Kit Worth Purchasing - Enjoy a convenient Screen Cleaner anytime, anywhere you need it. Your satisfaction is our top priority. We stand behind the quality of our products and that’s why, you shouldn’t be worrying at all. We manufacture the Best Screen Cleaner. and can be used for laptop cleaning kit, laptop screen cleaner, tv screen cleaner for smart tv. MacBook screen cleaner, monitor cleaner or screen cleaner spray for electronic devices with microfiber cleaning cloth
Why cooling towers drain water as blowdown
Operators periodically or continuously drain a controlled portion of the circulating water. This stream is called blowdown. Its purpose is to keep dissolved-mineral concentration within the range that the tower, piping and treatment programme can tolerate.
Fresh makeup water then replaces both the evaporated water and the blowdown. DOE FEMP describes blowdown as an operational part of maintaining consistent dissolved-mineral content in the recirculating condenser-water loop. Blowdown is not the same as evaporation: it remains liquid and normally goes to a wastewater-management route after any required onsite treatment.
Quick wins for a faster PC:
Repair Windows errors before they cause bigger problemsFix Now →Fix the driver behind crashes, sound loss and screen glitchesFind Drivers →Cycles of concentration: using less makeup water
“Cycles of concentration” compares the mineral concentration in circulating tower water with that in the incoming makeup supply. Running at more cycles means water stays in the tower longer before blowdown, which can reduce both makeup demand and wastewater volume. The limit is set by water chemistry, treatment capability, equipment materials, local rules and operating risk.
DOE FEMP cites a cooling-tower best-management practice in which increasing operation from three cycles to six reduces makeup water by 20% and blowdown by 50%. That is a result attributed to the cited practice, not a guaranteed outcome for every data centre. DOE notes that systems commonly operate at two to four cycles and that six or more may be possible when site conditions support it.
- Test makeup and circulating water before changing the control target.
- Check conductivity, scaling tendency, corrosion indicators and biological-control requirements.
- Confirm that valves, sensors and automated blowdown controls are calibrated.
- Verify that the receiving utility or permit allows the resulting discharge chemistry.
Where the water goes after cooling
Evaporated water enters the atmosphere
In an evaporative tower, the consumed fraction leaves as water vapour with the rejected heat. At the facility boundary, this is generally counted as consumption rather than discharge. Atmospheric moisture may later return as precipitation, but that natural cycle does not mean the same water is available to the facility in the same place or time.
Rank #3
- 【Large size】:Measuring 800 x 300 mm/ 31. 5×12 inches, which is wider and taller than others. Large mouse pad can perfectly fit your keyboard and mouse of any size, and there is also ample space for peripherals such as phones, tablets, etc.
- 【LED backlight mouse pad】:Blade Hawks RGB mouse pad provides 7 static modes and 7 dynamic modes will give you the options you are looking for. Power-off memory function remembers the last lighting mode you selected. The super glow fiber Chroma will give you a colorful gaming setup that you want.
- 【Anti-slip rubber base】:Made from Natural rubber, this gaming mousepad will firmly grip your desktop, allowing you to enjoy the ultimate precision in the games you are most passionate about. It also comes with a texture that enhances this ability even further.
- 【Smooth and waterproof surface】: Micro-textured cloth surface, for extremely precise mouse control and a smooth movement. When liquid splashes on the gaming mouse pad, it forms water droplets and slides down. Will not delay your work or gameplay.
- 【Plug and play】: This mouse and keyboard pad is powered by USB, plug and play, no driver required. One button control light modes. Press one time to change the lighting mode, press twice to change the brightness, press and hold about 3 seconds turn ON/OFF.
Blowdown goes to a treatment route
Blowdown contains concentrated dissolved minerals and any chemicals used in the cooling programme. Depending on local requirements, it may receive onsite treatment before being sent to a municipal wastewater utility or another permitted system. Microsoft says that, at the sites covered by its local explanation, non-evaporated water is typically returned to a local wastewater utility for treatment, subject to local regulations. That is a company-described practice, not a universal rule.
Some water remains in a recirculating loop
Water in a closed cooling loop can circulate between servers, pumps, heat exchangers and chillers without being discharged during normal operation. The loop still requires maintenance, leak response and eventual fluid management, and the surrounding facility may use water for humidification, sanitation or other purposes.
Reclaimed water and rainwater can replace potable supplies
Some operators use treated reclaimed water instead of drinking-water supplies where quality, infrastructure and permits make that practical. Rainwater capture can supplement supplies at selected sites. Microsoft reports both reclaimed or recycled-water use at some locations and rainwater capture at selected sites. Its local explanation also says some cooling water is reused two to five times before the non-evaporated portion is sent to a utility. These are site and company examples, not an industry-wide guarantee.
Whether a particular discharge is reused, treated, released or subject to additional limits must be confirmed in the operator’s environmental reports, local utility information and permit records. It is not accurate to assume that all discharged water returns directly to a watershed, is potable, or is reused for cooling.
How alternative cooling designs change the water pathway
| Cooling approach | How heat is rejected | Direct water implication | Main constraints |
|---|---|---|---|
| Cooling tower with evaporative heat rejection | Water evaporation carries heat from the condenser loop into outdoor air. | Requires makeup water for evaporation, blowdown, drift and leaks. | Water availability, chemistry, treatment, tower controls and climate. |
| Outside-air economizer | Suitable outdoor air removes heat directly when temperature and humidity permit. | Can reduce or avoid cooling-water use during suitable conditions. | Climate, air quality, humidity control, filtration and building design. |
| Air-cooled chiller or dry cooler | Fans move air across coils or radiators without a cooling tower’s evaporative process. | Usually avoids routine tower evaporation at the heat-rejection step. | Potentially higher electricity use, especially in hot weather. |
| Direct liquid cooling | Liquid captures heat close to chips or racks and transfers it to a coolant-distribution unit and heat-rejection equipment. | Can use a recirculating coolant loop; another part of the plant may still evaporate water. | Rack design, fluid compatibility, maintenance and heat-rejection architecture. |
| Closed-loop direct-to-chip design | Liquid circulates continuously between servers and chillers in a sealed circuit. | Can avoid ongoing cooling-water evaporation in the announced design. | Higher or different energy requirements, initial installation and site-specific heat rejection. |
Outside-air and air-cooled options are not automatically better in every location. A design that saves onsite water may consume more electricity, and electricity generation can have its own indirect water footprint. Climate, grid conditions, heat density, reliability requirements and water availability must be evaluated together.
Rank #4
- 【Softer and More Comfortable】Vaydeer wrist rest has unique diamond pattern, which is the combination of softness and aesthetics. The materials of wrist rest are improved into higher quality memory foam and covered with silky smooth lycra. The computer wrist rest makes you as comfortable and cushiony as like rest your wrists on clouds.
- 【Ergonomic Wrist Saver】The wrist rests for keyboard and mouse comes with a 17.32×3.15×0.83 inch keyboard wrist pad and a 5.94×3.15×0.83 inch mouse wrist support. Based on ergonomic design, the unique concave shape is the perfect fit for your wrist joints. The wrist rest pad fits most computer keyboards and laptops, improve hand and wrist posture, release your wrist and arm stress.
- 【Non-Slip Rubber Bottom】Featuring an anti-skid silicone base on the bottom, this wrist keyboard support stays firmly in place on your desk, preventing the padding from sliding around, ensuring stable and consistent wrist support during extended computer sessions.
- 【Better Experience & Pain Relief】Our keyboard arm rest is beneficial to alleviate the soreness caused by direct contact and friction between your arm and a hard desk surface, reducing the risk of wrist fatigue or carpal tunnel. The soft texture of memory foam can evenly distribute the pressure around your wrists and provide good support with just enough give.
- 【Helpful in Multiple Scenarios】Whether you're working, studying, writing, typing, gaming, this keyboard and mouse rest combo is an essential accessory to add comfort and support to your hands and wrists. It’s also a great gift for men, women, family, friend, coworker, gamer, teacher, etc.
What direct liquid cooling changes—and what it does not
Direct liquid cooling places a heat-transfer fluid near high-temperature components instead of relying only on room air. DOE FEMP describes arrangements in which a closed loop carries heat to a coolant-distribution unit and then to the facility’s heat-rejection system. That last stage may be dry, evaporative or hybrid, so “liquid cooled” does not by itself answer whether a site consumes water.
In August 2024, Microsoft announced a direct-to-chip design that is filled during construction and then continually recirculates water without a fresh cooling-water supply for the cooling loop. Microsoft says the design is intended to avoid evaporative cooling-water consumption and estimates savings of more than 125 million litres per data centre per year. That figure is the company’s design estimate, not an independently measured benchmark for all liquid-cooled facilities. Microsoft also states a nominal annual energy-use increase compared with its evaporative designs, illustrating why water and energy cannot be optimized in isolation.
Independent reader supportYour contribution helps us test, update, and keep practical guides available for everyone.How to compare a data centre’s water performance
Water Usage Effectiveness (WUE)
DOE FEMP defines site-based Water Usage Effectiveness as annual site water use in litres divided by annual IT-equipment energy use in kilowatt-hours:
WUE = annual site water use (litres) ÷ annual IT energy use (kWh)
Do these 3 things before closing this tab:
1Repair Windows errors before they cause bigger problems2Fix the driver behind crashes, sound loss and screen glitches3Clear out junk files and repair common Windows errorsMicrosoft describes its reported WUE as annual water used for humidification and cooling divided by annual IT kilowatt-hours. Before comparing two values, check whether both use the same numerator, facilities, reporting period and treatment of reclaimed water, discharge and non-IT loads.
Best Value
- 【No Drill Mounted】Cable management tray can be assembled in as little as 3 minutes or less-simply. Side clips easily clampe the edge of desk, pass through the holes on the sides, and secure excess cables with baskets. Desk cable management supports inward or outward installation to meet your needs in different scenarios, and provides you with great convenience when collecting and organizing wires.
- 【Rubber Pad Protects Desk】Wire organizer under desk built-in soft rubber pads on the clamp protect your desk from scratches, so you will not damage your furniture or office.
- 【Sturdy and Beautiful】Cord management under desk is made of high-quality carbon steel and holds about 15 lbs. The wire basket has 2 holes on each side of the tray to enable your cables to pass freely. Cable baskets are suitable for desk thickness use from 0.4" to 2.4".
- 【Space Saving & Keep Organized】Desk cable management tray holds all your power cords, outlet strips, USB hubs and computer transformers hidden from your feet, and the data cables will not enter the vacuum cleaner to keep your desk clean and tidy. Desk wire organizer is also suitable for use in the kitchen and outdoors.
- 【Reduce Safety Risks】Cable tray under desk keeps all plugs away from your kids, no more worry about tripping. Using 2 holes wire tray saves extra space, helps you easily cabling and wire protection. The mesh design is not easy to accumulate dust, but avoids safety accidents caused by messy wires.
| Reported value | Scope and qualification |
|---|---|
| 0.30 L/kWh, FY24 | Microsoft’s figure for data centres it fully owns and controls that had been operational for 12 months at the time of calculation. |
| 0.27 L/kWh, FY25 | Microsoft’s same stated dataset qualification; FY25 covered July 1, 2024 through June 30, 2025. |
| 0.49 L/kWh, 2021 | Microsoft’s previously reported global average, cited in a December 2024 comparison with its later figure and subject to the company’s stated scope. |
A lower WUE indicates less reported site water per unit of IT energy within that boundary. It does not describe the water intensity of a specific application, user request or machine-learning workload by itself.
Why a workload’s water footprint varies so widely
A 2025 review by Lei, Lu, Shehabi and Masanet reports more than a 10,000-fold variation across the analysed workload cases. The result does not mean every pair of data centres differs by that amount; it shows that water per unit of digital work can change dramatically under different assumptions and operating conditions.
The review identifies several determinants:
- Server efficiency and the proportion of time servers are doing useful work.
- Electricity-grid water-consumption factors, which represent indirect water associated with power generation.
- Cooling-system type and facility infrastructure efficiency.
- Climate zone and the resulting need for mechanical cooling or humidification.
- The share of inactive servers and the timing of hardware refresh cycles.
Direct facility water and indirect electricity-related water should be reported separately or clearly combined with an explained boundary. A WUE number cannot, on its own, answer the total water footprint of a workload.
A practical framework for evaluating a cooling system
- Map the heat path. Identify where heat leaves the chip, rack, room, chiller and final heat-rejection equipment.
- Separate water flows. Record withdrawals, makeup water, evaporation, blowdown, drift, leaks, recirculation and wastewater discharge independently.
- Check local conditions. Assess climate, water scarcity, source-water quality, wastewater capacity and permit limits.
- Compare energy and water together. Include the electricity consequences of dry cooling, economizers, pumps, fans and chillers.
- Define the metric boundary. State which buildings, months, water sources and IT loads are included before comparing WUE values.
- Plan for abnormal operation. Include drought restrictions, poor water quality, leaks, sensor failures, tower treatment problems and backup cooling modes.
There is no single cooling recipe that minimizes water in every location. The best outcome usually combines server and facility efficiency, suitable heat-rejection equipment, high utilization, careful water chemistry and a power supply with a transparent water boundary.
Quick Recap