Data centers can reuse heat by capturing warmth from servers, transferring it into a separate water loop, and using a heat pump when necessary to raise it to a temperature that a nearby building or district-heating network can use. Insulated pipes carry the heat to its destination. The process works best when the data center has a steady heat supply, a nearby user with matching demand, and infrastructure that can accept the heat—without compromising the facility’s cooling or computing reliability.

What happens to the energy used by a data center?

Servers and other computing equipment use electricity to process data. Nearly all of that electricity eventually becomes heat, which cooling systems must remove to keep equipment within safe operating conditions. The European Commission’s Joint Research Centre reported in 2020 that over 98% of energy consumed in a data center is eventually dissipated as waste heat. That figure describes heat dissipation; it does not mean 98% can be captured, delivered to a customer at a useful temperature, or sold economically. European Commission Joint Research Centre, 2020.

In a conventional facility, cooling equipment moves this heat out of the building and rejects it to the surrounding environment. A heat-reuse system adds equipment and a connection so some of that thermal energy can serve another purpose. The data center still needs dependable cooling; supplying heat is secondary to protecting the computing equipment.

What’s actually slowing this PC down?

Pick the symptom - the matching free tool is one click away.

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.

How does the heat-reuse process work?

  1. Cooling collects heat from computing equipment. Fans move warm air away from servers, or liquid cooling carries heat away from chips and other components. The exact source temperature depends on the cooling system and operating conditions.
  2. A heat exchanger transfers the energy. Warm air or cooling water heats a separate circuit, typically keeping the data center’s cooling loop distinct from the loop serving the customer. The exchanger transfers heat; it does not by itself raise its temperature.
  3. A heat pump lifts the temperature when needed. It uses electricity to move heat from a lower-temperature source to a higher-temperature delivery circuit. The greater the required temperature increase, the more important it is to evaluate the heat pump’s performance and electricity use for the project’s actual conditions.
  4. Pipes and controls connect the source to its user. Insulated pipework carries the heat to a building or district network. Pumps, valves and controls manage the flow and temperatures at the connection; the receiving system must be able to accept them.
  5. Storage or backup supply can help balance operation. A buffer or larger thermal store can hold heat for later use. Other heat sources may still be needed when demand exceeds the data center’s supply or when the timing does not match.

The International Energy Agency notes that heat pumps in district-heating systems can use waste-heat sources below 45°C. This is a statement about possible source temperatures, not a guaranteed efficiency, output or financial result for a particular installation. Performance depends on conditions such as source and delivery temperatures, equipment and electricity supply. IEA, “Heat pumps in district heating and cooling systems”.

#1 Best Overall
Senville LETO Mini Split Air Conditioner, Heat Pump, White, 12000 BTU
  • Alexa Enabled Mini Split AC/Heating System: Integrate with voice control or app, allowing you to adjust your mini split air conditioner from anywhere. Set routines for temperature changes.
  • Versatile 4-in-1 Mini Split: All-season solution with air conditioning, heat pump (functional up to 5F/-15C), dehumidifier, fan, and turbo function. Includes a DC Inverter that's UL Listed, AHRI Certified, and works with Alexa.
  • Stylish & Functional Mini Split AC: Suitable for both home and business. Provides performance without compromising aesthetics. Ideal for bedrooms, living areas, stores, eateries, and warehouses.
  • Installation Package Included: Includes indoor air handler, outdoor condenser, remote control, and installation kit with a 16ft. line set and communication wire. Pre-loaded with refrigerant for up to 25 ft. Note: Professional installation required.
  • 5 Year Manufacturer's Warranty: Includes 5 years on parts replacement and 5 years on the compressor. Senville offers complimentary technical assistance. Labor not included.

Why are heat pumps often necessary?

Heat leaving a data center may be warm enough for some nearby uses but too cool for a conventional district-heating network or a building’s heating system. A heat pump raises the temperature so the receiving system can use the energy. The heat exchanger and heat pump do different jobs: one transfers heat between circuits, while the other upgrades its temperature using electricity.

One design described in the IEA District Heating and Cooling implementation guide illustrates how substantial that lift can be. In the Braunschweig project design, data-center cooling water at 25°C is cooled to 18°C while a heat pump raises district-heating return water to a 70°C supply temperature. The recovered heat is intended to provide base load for a new residential area of 600 housing units. A connection to the existing network offers flexibility and peak shaving. These are project design details, not standard operating temperatures or a promise that another data center could supply the same number of homes. IEA DHC, Low-Temperature District Heating Implementation Guidebook, 2021.

Rank #2
Midea 12,000 BTU Window Air Conditioner with Heat, 550 Sq Ft
  • Multi-Season Comfort – This Midea 12000 BTU air conditioner is more versatile than standard AC units, offering powerful cooling and dehumidification in the summer and reliable supplemental heat in the fall. Best for large rooms up to 550 square feet. Note: Heat pump function will not operate if outside temperature is below 41°F.
  • Easy To Use – This air conditioner and heat unit is well-equipped with a digital LED display, 5 Modes, 3 speed settings, 24-hr Timer, and ECO energy saver. The Swing button adjusts the louvers up/down to direct the airflow. Wireless enabled, control your comfort from your smartphone and your smartwatch using the Midea SmartHome app or your voice via Alexa and Google Assistant. All functions can be set via the control panel, remote control, and app or voice assistant.
  • Save on Energy Without Sacrificing Comfort – This UL Listed, Energy Star certified air conditioner uses inverter technology to quickly cool your bedroom or apartment while providing up to 35% energy savings compared to the Energy Conservation Standard. With 12,000 BTUs, a CEER of 13.3, and 115V operation, this ac unit is loaded with features like auto shutoff, defrost control, and a washable front filter to maintain peak performance.
  • Ultra Low Noise Performance – This ac window unit operates at a noise level as low as 45 dBA. It’s such a quiet air conditioner that you will barely notice it, even when it’s on high. Enjoy your Zoom call, watch your favorite TV show, have a conversation. This ac unit for bedroom also creates just the right amount of white noise so you can get some rest.
  • Install Specs – This window air conditioner is designed to fit double hung windows with opening widths of 24 to 38.5 inches. Lower sash must open sufficiently to allow a clear vertical opening of 14.5 inches. AC window unit measures 19.41"W x 22.17"D x 13.9"H. Included components: 12000 btu window air conditioner, remote control, installation kit. This ac heater combo window unit is as a close as you can get to a mini split a/c. You may like it so much you just might buy two!

Who can use the recovered heat?

The most practical recipient depends on distance, temperature requirements, demand patterns and existing infrastructure. A close building may have a relatively direct connection, while a district-heating network can distribute heat to multiple users if its operating conditions and commercial arrangements allow the connection. An industrial heat user is another possible destination, but its specific process temperature and operating requirements must be checked. There is no universal ranking: the relevant comparison is between a particular data center’s heat profile and a real nearby customer’s needs.

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.
Potential heat user What the project must establish
Nearby building or development Whether the building’s heating loop can use the delivered temperature and flow, how far the connection must run, and whether demand coincides with available heat.
District-heating network Whether the network can accept the temperature, flow and return conditions; whether connection capacity is available; and whether the network operator will agree to the technical and commercial terms.
Industrial user Whether a nearby process needs heat at a compatible temperature and on a compatible schedule, and whether a viable connection and supply agreement can be made.

A short distance is helpful, but proximity alone does not establish feasibility. Existing network temperatures, flow rates, pressure, return temperatures, operating rules, connection costs and heat tariffs all affect whether a buyer can accept the heat. The IEA identifies district heating as an opportunity in the changing energy landscape, while the JRC report discusses technical and contractual acceptance as factors for a heat buyer. IEA, “Opportunities for district heating in the changing energy landscape,” 2025; European Commission Joint Research Centre, 2020.

Rank #3
Temprium 12000 BTU Mini Split Air Conditioner, 115V 22 SEER2 AC & Heat Pump
  • 【Unmatched Energy Efficiency with 22 SE2ER2】 Slash your utility bills with our advanced Inverter technology and industry-leading 22 SEER2 rating. Unlike standard units that constantly stop and start, our DC Inverter compressor adapts its speed to maintain the perfect temperature with minimal energy consumption. Paired with eco-friendly R32 refrigerant (GWP 675), this 115V mini split system delivers powerful 12,000 BTU cooling and 12,300 BTU heating while being kind to the environment. It's the smart, green choice for your home.
  • 【Powerful & Fast Year-Round Comfort】 Designed for spaces up to 750 sq. ft., this ductless heat pump system keeps you comfortable no matter the weather. Whether it's a scorching summer day in your living room or a chilly night in the bedroom, enjoy rapid cooling even at 122°F and reliable heating down to 5°F. Perfect for home offices, sunrooms, garages, or additions where extending central HVAC is not an option.
  • 【Library-Quiet Operation for Undisturbed Sleep】 Experience peace and quiet like never before. With noise levels as low as 23 dB (quieter than a whisper!), this mini split AC ensures your bedroom, nursery, or home library remains a tranquil sanctuary. Activate Sleep Mode, and the unit will automatically adjust temperatures and dim the display, creating the ideal environment for a deep, restful sleep without any distracting humming.
  • 【Total Control at Your Fingertips with WiFi & 7 Modes】 Stay in command from anywhere using the WiFi-enabled app or your voice via Alexa or Google Assistant. Forgot to turn off the AC? Use your phone. Want it cool before you arrive home? Schedule it. Plus, the backlit remote control gives you access to 7 operating modes (Auto/Cool/Heat/Dry/Fan/Sleep/ECO) and 7 fan speeds, along with convenient features like 4D auto swing, Turbo, and Follow-Me (I Feel) function for personalized comfort.
  • 【Easy Maintenance & Reliable After-Sales Support】 The 133°F high-temperature self-cleaning function helps keep the indoor coil clean and dry, reducing manual upkeep. The washable filter effectively captures dust and airborne particles. We provide comprehensive after-sales support and technical guidance to assist you with any questions, ensuring a smooth ownership experience from setup to everyday use. Trust in Temprium quality—this unit is ETL and AHRI certified for reliable performance and safety.

How to assess a heat-reuse project

A credible assessment starts with the data center’s actual heat profile and the receiving system’s actual requirements. A theoretical amount of heat in the cooling system is not the same as heat that can be recovered continuously, delivered at a useful temperature and accepted by a customer. The following sequence helps distinguish a promising location from a merely nearby one.

  1. Characterize the heat source. Establish where heat is available, at what temperatures, and how its amount and temperature vary over time. Do not assume the facility’s full energy use is recoverable or that server load remains constant.
  2. Identify a real heat user. Determine who would take the heat and what temperature, flow, pressure and schedule the user requires. A building, district network and industrial process can have different requirements.
  3. Calculate the temperature lift and electricity needs. Compare the source temperature with the delivery temperature. Evaluate heat-pump performance and power use under the project’s operating conditions rather than relying on a general source-temperature threshold.
  4. Check the physical connection. Measure the route and assess pipework, network access, thermal losses and connection capacity. Confirm that network flow and return-temperature conditions are compatible with the proposed operation.
  5. Match supply and demand over time. Compare availability with the user’s hourly and seasonal demand. Assess whether a buffer or larger thermal store is worthwhile and what backup heat is needed during peaks or shortfalls.
  6. Protect independent cooling and computing operations. Design the heat-reuse system so the data center can keep rejecting heat and cooling servers safely if the heat customer, network or heat-recovery equipment is unavailable.
  7. Agree on commercial and operating responsibilities. Data-center operators, heat-network companies, building owners and energy-service providers need clear arrangements for connection, tariffs, operating duties and risk allocation. Technical feasibility alone does not prove the heat can be sold profitably.
Independent reader supportYour contribution helps us test, update, and keep practical guides available for everyone.Support on Ko-Fi

What can prevent recovered heat from being useful?

The heat is too cool for the receiving system

Low-grade heat may not meet a network’s supply-temperature requirement without a heat pump. A larger temperature gap makes heat-pump performance and electricity consumption more important to the project assessment. A low-temperature network or a nearby user that can accept lower-temperature heat may require a smaller lift, but its actual requirements still need to be confirmed.

Rank #4
Senville LETO Mini Split Air Conditioner, Heat Pump, White, 24000 BTU
  • Alexa Enabled Mini Split AC/Heating System: Integrate with voice control or app, allowing you to adjust your mini split air conditioner from anywhere. Set routines for temperature changes
  • Versatile 4-in-1 Mini Split: All-season solution with air conditioning, heat pump functional up to 5F/-15C, dehumidifier, fan, and turbo function. Includes a DC Inverter that's UL Listed and AHRI Certified
  • Stylish & Functional Mini Split AC: Suitable for both home and business. Provides performance without compromising aesthetics for bedrooms, living areas, stores, eateries, and warehouses
  • Installation Package Included: Includes indoor air handler, outdoor condenser, remote control, and installation kit with a 16ft. line set and communication wire. Pre-loaded with refrigerant for up to 25 ft. Note: Professional installation required
  • 5 Year Manufacturer's Warranty: Includes 5 years on parts replacement and 5 years on the compressor. Senville offers complimentary technical assistance. Labor not included

The customer is too far away or cannot accept the connection

Longer pipe runs add capital cost and thermal losses. Even a nearby network may have constraints on temperatures, flow, pressure or return conditions, or may lack capacity to accept additional heat. The network operator must be technically and contractually willing to take it.

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.

Supply and demand do not happen at the same time

Data centers can produce heat throughout the year, while space-heating demand often falls in summer. Heat storage can shift some heat from a time of surplus to a time of need. IEA DHC materials describe pit, borehole and aquifer storage as options for storing summer heat for winter use, but storage adds equipment and cost, and winter peak demand may still require other heat sources. IEA DHC, decentralised renewable energy case studies; IEA DHC, InteGradeDH project.

Best Value
BLACK+DECKER Smart Portable Air Conditioner with Heat, 14,000 BTU, White
  • Four-in-One Unit: Our 14,000 BTU ASHRAE (10,200 BTU SACC) air conditioner also offers 10,000 BTU Heat for cold winter months. Portable AC with heat also functions as a dehumidifier & fan
  • Portable AC: Take this personal air conditioner (16.5” x 14.06” x 27.09) in rooms up to 700 sq. ft. Stay cool in the hot summer months and sleep well with this BLACK+DECKER ac unit for bedroom
  • Smart AC with Voice Control: This smart air conditioner allows Wi-Fi connectivity and can be controlled using our mobile app available on iOS and Google Play stores, and voice controlled by Amazon Alexa or Google Assistant
  • Follow Me Remote: Our portable AC unit comes with a full function remote control that features a FOLLOW ME function, which allows the remote to act as a thermostat for precise temperature control
  • Installation Kit: When it comes to fans that blow cold air, this indoor ac unit includes an easy-to-install window kit. A large, vented airflow outlet ushers in cool air

Server loads or network operation are less predictable than planned

A case study at TU Darmstadt found that available heat was lower and less constant than expected. It also describes network flow below assumptions raising return temperatures, which led to shutdown or inefficient heat-pump operation. The lesson is to design around conservative operating conditions and retain independent ways to cool the servers and reject heat. As the IEA DHC case-study report puts it: “The highest priority for the HPC operator is of course the fail-safe operation of the computer and not the utilization of the waste heat.” This is a case-study lesson, not a statement attributed to a named speaker. IEA DHC case studies.

The economics do not support the connection

Heat pumps and connecting infrastructure require investment, and heat pumps need enough annual operating hours to justify their cost. The project also needs workable agreements among the operator, network or building owner, and other parties involved. A heat stream can be technically recoverable yet have no viable buyer, tariff or allocation of operating risk.

What existing projects and estimates show

Operating examples and modeled potential demonstrate that reuse is possible, but they describe different kinds of evidence and should not be treated as interchangeable.

Special offer. See more information about Outbyte and uninstall instructions. Please review EULA and Privacy policy.
Evidence What it reports How to interpret it
Stockholm Data Parks; IEA Energy and AI report, 2025 More than 20 data centers connected to Stockholm’s heating network and 1.5% of system demand met. The report also cites a reduction of 50 g CO₂ per kWh of heat supplied, attributing that emissions figure to Covenant of Mayors (2023). A reported example for Stockholm, not a universal emissions saving or share that other networks should expect.
European proximity and heating-potential estimates; IEA Energy and AI report, 2025 About 10% of Europe’s building space-heat demand is within 5 kilometres of a data center that is also within a district-heating service area. The report estimates reused data-center heat could meet about 300 TWh of heating demand within a few kilometres by 2030, equivalent to 10% of European space-heating needs. The 10% proximity finding is a geographic screen, not proof of feasibility. The 300 TWh estimate depends on geography, recovery-rate and heat-pump assumptions; it is potential, not a forecast that every connection will be built or sold.
High-temperature heat-pump modeling; Oak Ridge National Laboratory, 2024 The paper models six configurations for supplying heat up to 120°C and applies them to a case study based on the Frontier high-performance-computing data center. It reports modeled reductions of 33,100–33,200 metric tons of CO₂ per year for a one-megawatt heat pump under its selected assumptions. These are model results, not measured annual savings from an installed heat pump at Frontier.

The Stockholm and Europe-wide figures come from the IEA’s 2025 Energy and AI report. IEA, Energy and AI, 2025. The high-temperature modeling is described by Oak Ridge National Laboratory, 2024.

Why waste heat can contribute, but not replace a heat system

Data centers can supply useful heat where their output, location and a customer’s needs align. The scale of that contribution depends on the share that can actually be recovered, the temperature a heat pump can deliver, network access and the timing of demand. The IEA’s European estimate is substantial, but it is conditional on those factors; it does not show that data centers can meet most heat demand on their own. A project therefore needs a customer, compatible infrastructure and a plan for the hours when recovered heat is unavailable or insufficient.